Cale_ST
Eletricista
evo nigdi nisam naletio na ovakvu temu pa nek se nađe
rješava san ove testove:
Online Marine Tests. Over 10,000 questions for Navigators, Engineers, Electricians and Catering staff.
pa naletio na par zgodnih pitanja
1) A six-pole asynchronous motor is connected to a power supply with a frequency of 50 Hz. If the rotor bar frequency is 2.3 Hz, what will be the speed of the motor ?
rjeÅ¡enje je 954RPM, e sad pitanje je kako doć do tog broja
2) Two 3 phase 4160 Volt, 60 Hz alternators are operated in parallel. The total load of the system is 1050 kW with power factor 0.75 lagging. If alternator No 1 is carrying 700 kW at 80 % power factor lagging _____
RJ: the Power Factor of alternator No 2 is lagging 0.658.
3)Alternator (A) 100 kVA runs parallel with alternator (B) 125 kVA, both are 3 phase, 240 V, 60 Hz. The load of A is 60 kW, 90% power factor and the load of B is 80 kW, 70 % power factor. What is the total load ?
RJ: 429.8 Amps
ajmo iskusni strujići, pomoć je dobro doÅ¡la kako meni tako i budućim čitateljima
rješava san ove testove:
Online Marine Tests. Over 10,000 questions for Navigators, Engineers, Electricians and Catering staff.
pa naletio na par zgodnih pitanja
1) A six-pole asynchronous motor is connected to a power supply with a frequency of 50 Hz. If the rotor bar frequency is 2.3 Hz, what will be the speed of the motor ?
rjeÅ¡enje je 954RPM, e sad pitanje je kako doć do tog broja
2) Two 3 phase 4160 Volt, 60 Hz alternators are operated in parallel. The total load of the system is 1050 kW with power factor 0.75 lagging. If alternator No 1 is carrying 700 kW at 80 % power factor lagging _____
RJ: the Power Factor of alternator No 2 is lagging 0.658.
3)Alternator (A) 100 kVA runs parallel with alternator (B) 125 kVA, both are 3 phase, 240 V, 60 Hz. The load of A is 60 kW, 90% power factor and the load of B is 80 kW, 70 % power factor. What is the total load ?
RJ: 429.8 Amps
ajmo iskusni strujići, pomoć je dobro doÅ¡la kako meni tako i budućim čitateljima
Last edited: